产品中心
ND 47-63 Miniature Circuit Breaker Series
ND 47-63 Miniature Circuit Breaker Series
ND 47-63 Miniature Circuit Breaker Series
ND 47-63 Miniature Circuit Breaker Series

ND 47-63 Miniature circuit breaker series

The product description

Miniature circuit breaker ND47-63 for lighting distribution system (Type C) or motor distribution system (type D).Mainly used for ac 50Hz, rated voltage to 230V, 400V, rated current to 1A~63A circuit overload, short circuit protection, at the same time can not frequently break electrical equipment and lighting lines under normal conditions.

Conformity with standard: GB10963.1 IEC 60898-1.

 

Normal working conditions

Environmental humidity: -5℃~40℃, the average value within 24 hours does not exceed 35℃. Altitude: the altitude of the installation site does not exceed 2000m.

Main technical parameters

■Main specification: Rated hole In: 1A 2A 3A 4A 5A 6A 10A 16A 20A 26A 32A 40A 50A 63A

■Number of poles: A monopole B ii and C tripole D quadrupole

■Type of instantaneous trip by circuit breaker: Type C (5In~10In); Type D (10IN-16in)

■Rated operation short-circuit breaking capacity: LCN = LCS: 6KA

■Mechanical and electrical life

   Electrical life: not less than 6000 mechanical life: not less than 20000 times.

 

Technical performance

The product type

Rated current

The number of Poles

Voltage

Breaking capacity (A)

ND47-63(C)

C1~C40

1

230/400

6000

C1~C40

2,3,4

400

6000

C50~C63

1

230/400

6000

C50~C63

2,3,4

400

6000

ND47-63(D)

D1~63

1

230/400

6000

D1~63

2,3,4

400

6000

 

Overcurrent protection characteristics

Rated current ln (A)

Initial state

The experiment of current

Set time

The expected results

Notes

1~63

cold

1.13ln

t≤1h

Don't trip

 

1~63

Immediately after a top test

1.45ln

t<1h

tripping

The current rises to the specified value steadily within 5s

1~32

cold

2.55ln

1s<t<60s

tripping

 

40~63

cold

2.55ln

1s<t<120s

tripping

 

1~63

cold

5ln

t≤0.1S

Don't trip

C Type

1~63

cold

10ln

t<0.1S

tripping

C Type

1~63

cold

10ln

t≤0.1s

Don't trip

D Type

1~63

cold

16ln

t<0.1s

tripping

D Type

 

Action characteristic curve

nd47 63xxdlqxl 4

 

Rated current ln(A)

1~6

10

16、20

25

32

40、50

63

Copper conductor nominal cross-sectional area(mm)²

1

1.5

2.5

4

6

10

16

Note: Wiring is applicable to wire connection below 25mm², torque2.0N·m。

 

Outline and Mounting Dimensions (mm)

Message feedback

News Center

Naidian Group is an electronic timer manufacturer and digital timer supplier, providing high-power relays, electronic time relays, digital timer relays, DC to AC solid state relays, and digital display timer relay knowledge popularization.

Return to work in the disease

On February 26, the production of NPOWER Group resumed. The director and manager of our company personall...

What are the key points in selecting a time relay?

There are five main advantages of choosing a time relay, namely, Control voltage, Functional requirements...

What is the future development trend of time relay?

Time relays are usually used in circuits with lower voltage or lower current to control circuits with hig...

GET A QUOTE

Get in Touch
×